EPC-B Rating Needed

Buildings with gas-fired humidifiers will find it difficult to meet the Minimum Energy Efficiency Standards.

Electric Humidifiers Popular

Using electric steam humidifiers rather than gas-fired reduces a building's reliance on fossil fuels.

Evaporative Cooling Benefits

Exhaust air evaporative cooling AHU strategy can reduce a building's cooling energy use by over 50%.

Decarbonisation of humidification in commerical buildings

Darren Bryant, Area Sales Manager at Condair, looks at how a commercial building using humidifiers can reduce its carbon footprint for humidity control and cooling.

Many commercial building operators are actively pursuing strategies to reduce carbon emissions to achieve the required Energy Performance Certificate (EPC) in time for the forthcoming regulatory changes. Current government targets are for all leased commercial buildings to have an EPC B-rating by 01/04/2030, although it’s expected this date may be shifted to as late as 2035.

So, what does this mean for humidification systems and what preparations, if any, are required to maintain the optimum indoor humidity whilst meeting the Minimum Energy Efficiency Standards (MEES)?

Any building operating gas-fired systems will find it increasingly difficult to achieve an EPC B-rating, given their reliance on fossil fuels. Gas-fired steam humidifiers have been popular across the UK, particularly in buildings needing high-capacity humidification. They offer big outputs with lower energy costs than electric steam humidifiers, as gas is obviously cheaper per kW than electricity.

Condair EL Electrode Steam Humidifier Electrodes Grid

We’ve recently seen many clients replace gas-fired humidifiers with electric steam humidifiers because they can be powered by renewable energy, reducing overall carbon emissions. The retrofit is a relatively simple swap, as the same space within the AHU is typically required. In many cases, the existing steam distribution system can remain in place, reducing installation costs and complexity.

However, because gas-fired humidifiers can provide high outputs from a single unit, an electric steam system will likely require a larger overall footprint than the gas unit it replaces. This should be considered during project planning. Replacing a 320 kg/h gas humidifier may require three or four electric humidifiers to achieve the same output. Fortunately, humidification systems of this size are often installed on rooftops, which can help alleviate space constraints.

If plant room space is limited, or if the available electrical capacity is insufficient to support an electric steam system, adiabatic humidifiers may provide a practical alternative. Cold water humidifiers installed inside the AHU can deliver high outputs but require pre-heating before the humidification section. The entering air conditions must be dry enough to absorb moisture from the humidifier. This pre-heating is typically provided by a heating coil connected to a gas boiler.

Unfortunately, this approach does not support carbon reduction goals, as the overall energy consumption and carbon emissions in this scenario would be comparable to those of the gas-fired humidifier being replaced.

However, often decarbonization initiatives involve replacing gas boilers with heat pump chillers, alongside exchanging other gas-fired systems. If this is the case, and the heating prior to the adiabatic humidifier can be achieved with a heat pump, the overall electrical load will be much less than using self-generating electric steam humidifiers due to the heat pump’s COP. As the adiabatic humidifier itself uses a very small amount of energy to simply circulate water, employing it in combination with a heat pump chiller, could result in the energy consumption being three times lower then self-generating electric steam humidifiers for the same humidity output.

Adiabatic humidifiers, such as the Condair ME, also offer excellent opportunities to reduce a building’s cooling energy consumption with associated carbon reductions. An evaporative humidifier will deliver 0.68kW of cooling for every 1kg of water evaporated. As a single unit will operate on less than 1kW of electricity whilst evaporating up to 1,000kg/h of water, the potential for low energy, high-capacity cooling is significant if it can be effectively employed.

Using direct air evaporative cooling (DEC) strategies to cool commercial buildings, rather than mechanical cooling, has a very limited potential. Buildings need to maintain mid-range indoor humidity levels, which a DEC strategy would struggle to do, and it relies on favorable outside air conditions for the water to evaporate. However, modern indirect AHU strategies, such as Exhaust Air Evaporative Cooling (EAEC), avoid both these limitations and offer consistent cooling performance.

Rather than humidifying and cooling the incoming airstream, an EAEC system cools the extract air from a room using an evaporative humidifier. Return air conditions are relatively stable and can be humidified close to saturation to achieve the maximum possible cooling effect. This cool, saturated return air is then passed through a heat exchanger before being exhausted outdoors. The heat exchanger transfers the cooling energy to the incoming airstream, reducing its temperature by up to 10K.

Because the humidity increase occurs only in the return air, there is no impact on indoor humidity levels. The efficiency of an EAEC system depends on the performance of the heat exchanger, but even with a modest 70% heat exchanger efficiency, a typical building in London could reduce its reliance on mechanical cooling by approximately 40% using this strategy. While it is not a universal solution, EAEC provides real and achievable benefits for energy reduction and decarbonization initiatives.

Decarbonization is being driven by regulatory requirements and financial risk. Upgrading heating, cooling, and humidification systems will soon become essential for building owners and landlords, as failure to meet Minimum Energy Efficiency Standards could prevent a building from being legally leased. With many properties requiring upgrades, competition for skilled labor and building materials is likely to increase as deadlines approach.

Early planning can help avoid regulatory penalties and lost rental revenue. Condair provides free, expert guidance for building operators and facility managers exploring humidification and evaporative cooling solutions to help achieve or exceed the EPC B rating before the deadline.

Share this article

Need more information
or expert guidance?

Get in Touch with Condair

Contact Your Local Condair Rep

Contact your local Condair representative who can help you with all of your humidification, dehumidification, and evaporative cooling projects.

Contact Condair in North America

Not sure where to start? Contact us and we’ll direct your enquiry to the appropriate Condair representative or department.